Alarm
Messages in the „Exploitation – Mode“
Target Temperature:
|
Alarm appears when Ttarget is not
inside
TS22S1<T2.2<TS22S3
Default-value: TS22S1 = 20K,
TS22S3 = 21K
|
Condenser Temperature:
|
Alarm appears when Tcondenser is not inside
TS21S1<T2.1<TS21S3
Default-value:
TS21S1 = 20K, TS21S3 = 21K
|
Target
Pressure:
|
Alarm
appears when Ptarget is not inside
PT02S1<PT02<PT02S2
Default-value: PT02S1 = 800 mbar, PT02S2 = 1200 mbar
|
Storage
Pressure:
|
Alarm
appears when Pstorage (PT01) < PT01S1
Default-value: PT01S1 = 1050 mbar
|
Vacuum
Chamber:
|
Alarm
appears when the Isolationsvacuum (IG01) is not < IG01S1
Default-value: IG01S1 = 10-6 mbar
|
Compressor (CP):
Alarm appears when the Compressor has been stopped
Pneumatic Valve (PV01):
Alarm appears when the Valve PV01 has been opened
Rough
Pump (RP01): Alarm
appears when the Rough Pump RP01 has been stopped
Turbo
Pump (TP01):
Alarm
appears when the Turbo Pump TP01 has been stopped